proyectos@eomingenieros.com     +51 927 958 269                                                                                      CERTIFICACIONES

Latino-Fill-05: The best low fouling Counter flow Sea water Cooling Tower Film Fill

The sea water cooling tower film fill is qualified worldwide as the best film fill combining low fouling properties with good thermal performance.

It’s well proven technology of non-contact sheets, which combined with smooth horizontal corrugations, allows even water distribution over the sheet and water rotation for good contact with air and resistance to deposition of solids. The vertical flute design of this sea water cooling tower film fill allows self drainage of the cores and reduces the pressure drop.

It is well adapted to any induced draft or natural draft cooling tower using poor quality inductrial water particularly sea water. It’s also suitable ofr otehr severe appications such as laminated decanting and washing gas.

Categoría:

Descripción

Quick Details

Condition: New Cooling Type: Counter Flow Material: PVC
Place of Origin: Tianjin, China (Mainland) Brand Name: LATINO Model Number: Latino-Fill-05
Voltage: NO Power(W): NO Dimension (L*W*H): 2032*500mm or n *508mm
Weight: based on the required thickness Certification: CTI Warranty: 12 Months
After-sales service Provided: No overseas service provided Vicat Softening Temp.: ≥ 68℃ Density: 1.38+/-0.5
Colour: Black Thickness: 0.25 – 0.4mm Fire Classfication: M2
Emptying factor: >95% Sheet pitch: 20mm Maximum deris size: 17mm (diameter)
Tolerance on thickness +/-10% Tolerance on Width: +/-5%

 

The best low fouling Counter flow Sea water Cooling Tower Film Fill

The sea water cooling tower film fill is qualified worldwide as the best film fill combining low fouling properties with good thermal performance.

It’s well proven technology of non-contact sheets, which combined with smooth horizontal corrugations, allows even water distribution over the sheet and water rotation for good contact with air and resistance to deposition of solids. The vertical flute design of this sea water cooling tower film fill allows self drainage of the cores and reduces the pressure drop.

It is well adapted to any induced draft or natural draft cooling tower using poor quality inductrial water particularly sea water. It’s also suitable ofr otehr severe appications such as laminated decanting and washing gas.

This type fill has proven its efficiency for more than 20 years.

Material PVC Typical moudle length  

2032mm (n*55.5mm)

Fire Classification M2 Typical specific weight 21.0kg/m3+/-5% (0.30mm)
Sheet thickness  0.25-0.40mm Color Black
Sheet pitch 20 mm Specific heat exchange surface 127.0m2/m3

 

 

 